SINGLE PHASE HIGH CURRENT TRANSFORMER, 72 KVA

OUTPUT 72 VAC, 1000 AMPS, P/N 9512L

Specifications:

    • High Current Transformer, 72 KVA, 1 PH, 60 Hz, P/N 9512L
    • Dual coil construction, each coil has three secondaries
    • Primary (1, 4): 480 VAC, 150 Amps
    • Secondary (5, 6): 12 VAC, 1000 Amps
    • Secondary (7, 8): 12 VAC, 1000 Amps
    • Secondary (9, 10): 12 VAC, 1000 Amps
    • Secondary (11, 12): 12 VAC, 1000 Amps
    • Secondary (13, 14): 12 VAC, 1000 Amps
    • Secondary (15, 16): 12 VAC, 1000 Amps
    • Six secondaries can be connected in series to get 72 VAC, 1000 Amps
    • Six secondaries can be connected in parallel to get 12 VAC, 6000 Amps
    • Jumpers are not provided
    • Copper windings
    • Approvals: None
    • Primary copper bus bars are 1″ x 1/4″ thick with one hole
    • Secondary copper bus bars are 3″ x 4″ x 1/4″ thick with one hole
    • Open core & coil: 25″H x 25″W x 25″D
    • Estimated weight: 700 lbs.

The schematic diagram is shown below:

 

 

The estimated dimensions of the transformer are shown below:

 

 

Six secondaries can be connected in series as follow to get 72 VAC, 1000 Amps output. Jumpers are not provided

 

 

Six secondaries can be connected in parallel as follow to get 12 VAC, 6000 Amps output. Jumpers are not provided.

 

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.