Current Limiting Reactor, 800 Continuous Amps, 480 VAC L-L,
40000 Available Amps 25000 Fault Limit Amps, P/N KK-10C
A current-limiting reactor is used when the prospective short-circuit current in a distribution or transmission system is calculated to exceed the interrupting rating of the associated switchgear. The inductive reactance is chosen to be low enough for an acceptable voltage drop during normal operation, but high enough to restrict a short circuit to the rating of the switchgear. The amount of protection that a current-limiting reactor offers depends upon the percentage increase in impedance that it provides for the system.
The main motive for using current-limiting reactors is to reduce short-circuit currents so that circuit breakers with lower short-circuit breaking capacity can be used. They can also be used to protect other system components from high current levels and to limit the inrush current when starting a large motor.
The customer application is shown below:
Current Limiting Reactor, Three Phase
Inductance Calculation
Specifications:
- CLR, 800 Amps continuous, 40000 available Amps, 25000 Amps desired fault current, P/N KK-10C
- Copper windings
- Approvals: none
- System shipping weight: 750 lbs. (one enclosure)
- Calculated Inductance Value: 23 uH, 800 Amps continuous
- Three inductors in one indoor enclosure (68″H x 65″W x 44″D)
The detail of one Air Core Inductor, KK-10C-1 is shown below. Three KK-10C-1 are required for one CLR KK-10C.
KK-10C-1. Three are required per system
Specifications:
- Air Core Inductor, P/N KK-10C-1
- L (1, 2) = 24.1 uH
- Continuous Current: 800 Amps
- Frequency: 60 Hz
- Copper windings
- Approvals: None
- Copper bus bars are 2″ x 1/4″ thick with one hole
- Estimated weight: 150 lbs.
- One CLR consists of three separate air core inductors in one indoor enclosure
P/N KK-010B-1 consists of two modules to offer 800 Amps continuous. shown below is one module. Each module is capable of 500 Amps continuous.
Three KK-10C-1 are housed inside an indoor enclosure as shown below: Three each of KK-10C-1 make one CLR system KK-10C
The photo of the enclosure is shown below:
Three Inductors in one enclosure
All our CLR’s are custom-built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.