Current Limiting Reactor, 3000 continuous Amps, 480 VAC L-L,

55000 Available Amps, 22000 Fault Limit Amps, P/N KK-03

 

A current-limiting reactor is used when the prospective short-circuit current in a distribution or transmission system is calculated to exceed the interrupting rating of the associated switchgear. The inductive reactance is chosen to be low enough for an acceptable voltage drop during normal operation, but high enough to restrict a short circuit to the rating of the switchgear. The amount of protection that a current-limiting reactor offers depends upon the percentage increase in impedance that it provides for the system.

The main motive for using current-limiting reactors is to reduce short-circuit currents so that circuit breakers with lower short-circuit breaking capacity can be used. They can also be used to protect other system components from high current levels and to limit the inrush current when starting a large motor.

The customer application is shown below:

 

Current Limiting Reactor, Three Phase

 

Inductance Calculation

Specifications:

A. CLR, 3000 Amps continuous, 480 VAC L-L, 55000 available Amps, 22000 Amps desired fault current, P/N KK-03
B. Copper windings
C. Approvals: none
D. System shipping weight: 1800 lbs. (three enclosures)
E. Calculated Inductance Value: 33.3 uH, 3000 Amps continuous
F. Three inductors in three separate enclosures (50″H x 50″W x 50″D)

The detail of one Air Core Inductor, KK-03A is shown below. Three KK-03A are required for one CLR KK-03.

 KK-03A, Three are required per system

Notes:

    1. Air Core Inductor, P/N KK-03A
    2. L (1, 2) = 33.3 uH
    3. Continuous Current: 3000 Amps
    4. Frequency: 60 Hz
    5. Copper windings
    6. Approvals: None
    7. Copper bus bars are 4″ x 1/4″ thick with two holes
    8. One CLR consists of three separate air core inductors in three separate outdoor enclosures

P/N KK-03 consists of six modules to offer 3000 Amps continuous. shown below is one module. Each module is capable of 500 Amps continuously.

The Air Core Inductor is installed inside the enclosure, P/N KK-03A

Each KK-03A is housed inside an indoor enclosure (50″H x 50″W x 50″D) as shown below. Six 500 Amps modules stacked vertically to build a 3000 Amps inductor.

 

Notes:

1. (A), (B), (C) are 10-inch minimum

Three Air Core Inductors are housed in three separate enclosures:

 

 

One complete Current Limiting Reactor System, P/N KK-03

Consisting of three separate inductors in three separate enclosures

All our CLRs are custom-built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.