CLR, 55 uH, 300 Amps, 480 VAC, 3 PH, 60 Hz, P/N BA-02

The calculations of the inductance are shown below:

    • V L-L = 480 VAC
    • V L-N = 277 VAC
    • Frequency = 60 Hz
    • Desired Fault Current IL1: 10000 Amps
    • Available Fault Current IL2= 25000 Amps
    • L = [1.25 x V L-N x (1/ IL1 – 1/ IL2)] / (2 x π x 60)
    • Inductance = [1.25 x 277 x (1/10000 – 1/25000)] / (2 x 3.142 x 60) = 55 uH

Specifications:

    • Air Core Reactor, P/N BA-02
    • Inductance = 55 uH
    • Impedance = 20.7 milliohms
    • Continuous current: 300 Amps
    • Available fault current: 25000 Amps
    • Limit fault current: 10000 Amps
    • Voltage: 480 VAC L-L
    • Three inductors are required for one complete CLR system
    • Enclosure dimensions: 111”H x 54”W x 54”D
    • Estimated weight: TBD