Specifications:
-
- Dry Type Transformer, 300 KVA, 3 PH, 60 Hz, P/N MG-267
- Primary: 208 VAC L-L, Delta
- Primary Taps: 2-2.5% FCAN and 4-2.5% FCBN
- Secondary: 480 VAC L-L Wye with a neutral, 277 VAC L-N
- Aluminum Windings
- Approvals: UL / CSA listed
- K Factor: K-13
- Temperature Rise: 150 degrees C
- Outdoor Enclosure with Rain Hood: 66.00″H x 50.50″W x 40.50″D
- Estimated weight: 2700 lbs.
The schematic diagram is shown below:
The details of the enclosure are shown below.
The photo of the enclosure is shown for reference:
All our transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.