THREE PHASE MULTI TAP TRANSFORMER
5.8 KVA, P/N 19653

Specifications:

  • Multi-Tap Transformer, 5.8 KVA, 3 PH, 60 Hz, P/N 19653
  • Primary (X1, X2, X3): 423/447/470/494/517 VAC L-L, 7.12 Amps, Delta
  • (470 VAC L-L is the nominal, +/- 5% and +/- 10%)
  • Three jumpers are provided for the selection of primary voltages
  • Secondary (H1, H2, H3, N): 1370 VAC L-L, 2.43 Amps, Wye, 791 VAC L-N
  • Copper windings
  • Approvals: None
  • Electrostatic Shield between primary and secondary, connected to the frame
  • Primary and secondary copper connections are 5/16-18-1/2 silicon bronze
  • Open core & coil: 14.5”W x 10”D x 14”H
  • Estimated weight: 180 lbs.

The photo of the transformer is shown below:

 

 

The schematic diagram is shown below:

 

 

To discuss your specific application, please call us at (714) 624-4740, or send us an email at quote@lcmagnetics.com.