Specifications:
- Air Core Reactor, P/N 6885L
- Inductance = 10 uH
- Impedance = 0.0038 Ohms
- Continuous current: 1600 Amps
- Available fault current: 70000 Amps
- Limit fault current: 42000 Amps
- Voltage: 480 VAC L-L, 277 VAC L-N
- Voltage drop: 2.2%
- Terminal: NEMA 4 bolt hole pattern
- Three reactors are stacked one above the other in a vertical fashion
- Enclosure with louvers: 97”H x 60”W x 60”D
- ANSI TR-202 base insulators (1 for each reactor)


- Minimum spacing center to center is 29”
- Outside coil diameter is 17”
- Terminals: NEMA 4 bolt hole pattern
- Approximate weight: 330 lbs
- 3 seconds thermal: 53.3 KA, mechanical peak: 141.4 KA
- Minimum clearance to small magnetic objects not forming closed loops
-
- A = 20.5”
- B = 3”
- For large magnetic objects & magnetic objects forming closed loops
- A = 29”
- B = 12”
- Must be weather protected
All our auto transformers are custom built to order. To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at info@LCMAGNETICS.COM.