MULTI TAP TRANSFORMER, 26 KVA, P/N 19127N

Specifications:

    • Multi Tap Transformer, 26 KVA, 3 PH, 60 Hz, P/N 19127N
    • Primary: 480 VAC L-L, 31.5 Amps, Wye with a neutral N1
    • Secondary: 153 / 192 / 232 / 272 VAC L-L, 98 Amps max, Wye with neutral N2
    • If 480 VAC is applied at (1, 1, 1), output is full load
    • If 480 VAC is applied at (2, 2, 2), output is partial load
    • Copper winding construction
    • Primary and secondary Copper bus bars are 1/8″ x 5/8″ with one hole
    • Indoor enclosure, 24″H x 18″W x 16″D
    • All connections are inside the enclosure

The photo of the transformer  and the enclosure is shown below:

 

PHOTO, 19127N

 

The schematic of the transformer with five primary taps and twelve secondary taps is shown below:

 

SCHEMATIC, 19127N

 

To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.