DRY TYPE ISOLATION TRANSFORMER, 75 KVA, PRIMARY 220 VAC DELTA, SECONDARY 480 VAC WYE, ALUMINUM WINDING, P/N MG-135
Specifications:
-
- Dry Type Isolation Transformer, 75 KVA, 3 PH, 60 Hz, P/N MG-135
- Primary (X1, X2, X3): 220 VAC L-L, Delta
- Primary taps: 2-2.5% FCAN and 4-2.5% FCBN
- Secondary (H1, H2, H3): 480 VAC L-L, Wye with neutral N (H0), 277 VAC L-N
- Aluminum windings
- Approvals: CSA / UL listed, K-Factor: K-1
- Temperature rise: 150 degrees C
- Enclosure dimensions: 38.00”H x 28.50”W x 19.50”D
- Weight: 650 lbs.
The photo of the transformer is shown below:
The schematic diagram is shown below. Primary taps are not shown.
The Primary Taps are shown below in Table A. Three jumpers are used to select primary of 220 VAC, 3 PH L-L, Delta.
Table A
The photo of the transformer before shipment is shown below: Shipment dimensions: 48”H x 42”W x 28”D. Weight: 700 lbs.