THREE PHASE MULTI TAP TRANSFORMER
50 KVA, P/N MG-87B
Specifications:
- Dry Type Isolation Transformer, 50 KVA, 3 PH, 60 Hz, P/N MG-87B
- Primary (X1, X2, X3): 208 VAC L-L, Delta
- Primary taps: 2-2.5% FCAN and 4-2.5% FCBN
- Secondary (H1, H2, H3): 575 VAC L-L, Wye with neutral N (H0), 332 VAC L-N
- Secondary (H4, H5, H6): 480 VAC L-L, Wye with neutral N (H0), 277 VAC L-N
- Copper windings
- Approvals: CSA / UL listed, K-Factor: K-1
- Temperature rise: 150 degrees C
- NEMA 3R Enclosure: 38.50″H x 28.50″W x 20.00″D.
- Weight: 600 lbs.
The photos of the secondary side is shown below:
The photo of the transformer is shown below:
The schematic diagram is shown below. Primary taps are not shown.
The Primary Taps are shown below in Table A. Three jumpers are used to select primary of 208 VAC, 3 PH L-L, Delta.
Table A
The photo of the transformer before shipment is shown below:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.