SCOTT T TRANSFORMER
5 KVA, P/N 18713N
Scott T Transformers offer two single-phase outputs and not one single-phase output.
Scott T Transformers cannot be used to create only one single-phase output.
Specifications:
- Scott Configuration Transformer, 5 KVA, P/N 18713N
- Input: 240 VAC, 3 PH, 60 HZ
- Output MAIN: 120 VAC, 20.8 A, 1 PH
- Output TEASER: 120 VAC, 20.8 A, 1 PH
- Indoor enclosure: 24” H x 18” W x 16” D
- MAIN and TEASER are 90° out of phase.
- T1/T2 Jumper is provided with the unit.
The photo of the Scott configuration transformer is shown below:
The schematic diagram is shown below. MAIN and TEASER outputs must not be connected in series or in parallel:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.