750 KVA TRANSFORMER
Specifications:
- Transformer: 750 KVA, 3 PH, 60 Hz, P/N 10358L8
- Primary (H1, H2, H3): 480 VAC L-L, Delta, 902.1 Amps
- Secondary (X1, X2, X3, X0): 4160 VAC L-L, Wye, 104.1 Amps
- Secondary taps: +/- 10%, 1.25% per step (17 taps in total).
- Application: Variable-speed drive (VSD) for electrical submersible pump
- Copper windings
- ONAN Cooling – Non-PCB Mineral Oil
- Temperature Rise: 65 degrees C
- Dimensions: 120” W x 92” H x 72” D
- Control Panel will automatically select the tap to provide the specified output voltage.
- NEMA 3R Enclosure
- Core: 5000 lbs.
- Copper: 1500 lbs.
- Estimated weight: 12500 lbs. or TBD
The photo of the enclosure is shown below.
To discuss your specific application, please call our number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.
CONTACT FOR A FREE QUOTE
Need a replacement for urgent and obsolete transformers and inductors?
Our engineers can respond within the hour.
EMAIL: quote@lcmagnetics.com
PHONE: (714) 624-4740
L/C MAGNETICS INC.
MANFACTURER, RESELLER, AND DISTRIBUTOR OF CUSTOM TRANSFORMERS AND INDUCTORS
DRY TYPE TO OIL FILLED PRODUCTS FROM 0.1 KVA TO 50 MVA
CELEBRATING 37 YEARS IN BUSINESS
CARL E. HOLMES COMPANY -- CEHCO
MANUFACTURER OF CUSTOM DC RECTIFIERS, TRANSFORMER RECTIFIER ASSEMBLIES, AND POWER SUPPLIES
DIVISION OF L/C MAGNETICS
RECTIFIER SPECIALIST SINCE 1945