24-PULSE 748 KVA ISOLATION TRANSFORMER
Specifications:
- 24-Pulse Isolation Transformer: 748 KVA, 3 PH, 60 Hz, P/N 10358L3
- Primary (H1, H2, H3): 480 VAC L-L, Delta
- Secondary 1: 480 VAC L-L, Delta, 187 KVA
- Secondary 2: 480 VAC L-L, Wye, 187 KVA
- Secondary 3: 480 VAC L-L, Delta, 187 KVA
- Secondary 4: 480 VAC L-L, Wye, 187 KVA
- Application: Variable-speed drive (VSD) for electrical submersible pump
- Copper windings
- Primary connections are 0.25″ x 2.00” copper bus bas
- Secondary connections are 0.25” x 1.50” copper bus bars
- ONAN Cooling – Non-PCB Mineral Oil
- Temperature Rise: 65 degrees C
- Dimensions: 96” W x 84” H x 66” D
- Two Cores are used: 3300 lbs.
- Copper: 1220 lbs.
- Estimated weight: 8400 lbs. or TBD
The photo of the indoor enclosure is shown below. All terminations are enclosed on the upper cover.