(714) 624-4740 quote@lcmagnetics.com

24-PULSE 748 KVA ISOLATION TRANSFORMER

Specifications:

  • 24-Pulse Isolation Transformer: 748 KVA, 3 PH, 60 Hz, P/N 10358L3
  • Primary (H1, H2, H3): 480 VAC L-L, Delta
  • Secondary 1: 480 VAC L-L, Delta, 187 KVA
  • Secondary 2: 480 VAC L-L, Wye, 187 KVA
  • Secondary 3: 480 VAC L-L, Delta, 187 KVA
  • Secondary 4: 480 VAC L-L, Wye, 187 KVA
  • Application: Variable-speed drive (VSD) for electrical submersible pump
  • Copper windings
  • Primary connections are 0.25″ x 2.00” copper bus bas
  • Secondary connections are 0.25” x 1.50” copper bus bars
  • ONAN Cooling – Non-PCB Mineral Oil
  • Temperature Rise: 65 degrees C
  • Dimensions: 96” W x 84” H x 66” D
  • Two Cores are used: 3300 lbs.
  • Copper: 1220 lbs.
  • Estimated weight: 8400 lbs. or TBD

The photo of the indoor enclosure is shown below. All terminations are enclosed on the upper cover.

To discuss your specific application, please call our number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.

CONTACT FOR A FREE QUOTE

Need a replacement for urgent and obsolete transformers and inductors?

Our engineers can respond within the hour.

EMAIL: quote@lcmagnetics.com

PHONE: (714) 624-4740

L/C MAGNETICS INC.

MANFACTURER, RESELLER, AND DISTRIBUTOR OF CUSTOM TRANSFORMERS AND INDUCTORS

DRY TYPE TO OIL FILLED PRODUCTS FROM 0.1 KVA TO 50 MVA

CELEBRATING 37 YEARS IN BUSINESS

CARL E. HOLMES COMPANY -- CEHCO

MANUFACTURER OF CUSTOM DC RECTIFIERS, TRANSFORMER RECTIFIER ASSEMBLIES, AND POWER SUPPLIES

DIVISION OF L/C MAGNETICS

RECTIFIER SPECIALIST SINCE 1945