11 KVA LOAD BANK, P/N 9384L
Calculation of Inductance:
-
- Input Voltage = 208 VAC L-L, 120 VAC L-N
- Continuous Current = 30 Amps
- Frequency = 400 Hz
- R = V / I = 120 VAC / 30 Amps = 4 Ohms
- R = 2 x π x F x L
- Therefore, L = R / (2 x π x F) = 4 / (2 x 3.142 x 400) = 1.6 mH
The customer application is shown below. Three each 1.6 mH, 30 Amp Inductors will be connected in a Wye fashion to offer an 11 KVA Load Bank.
The details of the 1.6 mH, 30 Amp Inductor are shown below:
Specifications:
- Gapped Inductor, P/N 9384L
- L (1, 2) = 1.6 mH ± 25%, 30 Amps, 400 Hz
- Copper windings
- Approvals: None
- Copper bus bars are 1/4″ x 1″ thick with one hole
- Open core and coil: 5″H x 5.5″W x 5″D approximately
- Estimated weight: 25 lbs.
A photo of a similar Inductor is shown for reference below:
To discuss your specific application, please call our phone number at (714) 624-4740, or send us an email at quote@lcmagnetics.com.